Sign In | Join Free | My chinalane.org
chinalane.org
Products
Search by Category
Home > Inverters & Converters >

High Frequency online UPS, Uninterrupted Power Supply 0.9 Output 10-20KVA

Categories High Frequency Online UPS
Place of Origin: China
Brand Name: SOROTEC
Certification: CE,ROHS,ISO9000
MOQ: USD10000
Packaging Details: Standard Exported Cartons and Pallets
Delivery Time: Within 15-30days after receiving your 30% TT deposit
Payment Terms: 30% TT in advance, the balance before shipping
Supply Ability: 10000PCS/Month for Inverter and line Interactive UPS; Advance 3000PCS/Month for Online UPS
Model Number: HP9315C 10 - 20KVA
Rated Voltage: 380VAC 3phase with ground
Rated Frequency: 50/60HZ
VoltageRange: 115~300VAC
FrequencyRange: 50HZ:(46~54HZ);60HZ:(56HZ~64HZ)
Power Factor: >0.98
Voltage Regulation: 208/220/230/240X(1±2%)VAC
Frequency Regulation: 50/60HZ±0.05 Hz
Current Crest Ratio: 3:1
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    High Frequency online UPS, Uninterrupted Power Supply 0.9 Output 10-20KVA

    High Frequency online UPS, Uninterrupted Power Supply HP9115C1-20KVA 1-3K 0.8Output

    Key Features:

    1.0.9 Output Factor UPS


    2. Large blue back light LCD for detailed Real-time UPS status display.


    3. Advanced online pure sine wave power supply system, with bypass repair switch, It can provide a reliable, high quality AC power source to the precision equipments, can be used widely in different fields.


    4. Widely used to computer equipments, telecommunication systems and Industrial automatic control equipments.


    5. Truly online design, different from offline, it can adjust the input voltage, filtering, when the AC break off, the UPS will provide an uninterruptible power source from the backup batteries.


    6. UPS will change to bypass mode when overloading or inverter fault, when overloading remove, UPS will turn to inverter mode automatically.


    7. N+N Parallel Redundancy and Capacity expansion for 6-20K(up to three units)


    Applications:

    Servers, Data-center, critical network devices, Sensitive electronic equipment, Telecom…


    Technical Specifications of Online UPS HP9115C 1-10K

    Model

    HP9315C 10-20KVA

    10KT-XL

    15KT-XL

    20KT-XL

    Rated Power

    10KVA/9000W

    15KVA/13500W

    20KVA/18000W

    Rated Voltage

    380VAC 3phase with ground

    Rated Frequency

    50/60HZ

    Input

    VoltageRange

    115~300VAC

    FrequencyRange

    50HZ:(46~54HZ);60HZ:(56HZ~64HZ)

    Power Factor

    >0.98

    Output

    Voltage Regulation

    208/220/230/240X(1±2%)VAC

    Frequency Regulation

    50/60HZ±0.05 Hz

    Power factor

    0.9

    Voltage distortion

    Linear load<3% Non-Linear load<6%

    Overload

    Capability

    110%~150% for 30s change to bypass model, Recover after load normal

    Current Crest Ratio

    3:1

    Transfer time

    0ms(AC mode→ Battery mode)

    Battery

    DC Voltage

    240VDC

    Recharge Current

    4.2A

    Display

    LCD

    Display input/output Voltage, Frequency, Battery voltage, Battery capacity, Loading rate.

    Communication

    Interface

    Smart RS232, SNMP(optional) , USB(optional)

    Environment

    Operation Temperature

    0~40℃

    Humidity

    0~95%non-condensing

    Storage Temperature

    -25℃~55℃

    Sea level elevation

    <1500m

    Noise Level(1m)

    <55dB

    Physical Characteristic

    Weight(KG)

    N.W.

    47

    54

    54

    G.W.

    53

    60

    60

    Dimension(D x W x H)mm

    570X260 X717


    APPLICATION OF OUR PRODUCT

    1. Living house and home building

    2. Office building, factory and warehouse

    3. Shopping mall, stadium and so on

    4. Power station, field operation and some huge engineer construction

    5. suitable for various home appliance, Office equipment,Journeys, Camping, Tents, Boat Trip


    COMPANY SHOW

    Introduction of Company

    Shenzhen SORO Electronics Co., Ltd is a professional UPS and inverter manufacturer in the field of power electronics for 13 years. We have two large production UPS sites, Zhejiang and Shenzhen. We have own our SMT department. SORO UPS has been a leading enterprise in the UPS industry in China.

    Since established, The company has carried out three strategies: operation innovation strategy, people-oriented strategy , technical guidance strategy, and implemented strict scientific management with full-fledged quality management system. The company invests 10% of its annual revenue in researching and development every year. We had international advanced equipments for developing , testing and producing. SORO UPS invited the best technical elites at home, meanwhile, the company established perfect cooperation relationship with domestic scientific research units and academies, to strive for making products that reach advanced world standards.


    WHY CHOOSE US ?

    1, QC Control

    The company ranks first in passing the ISO9001 international quality system certification.We established a complete quality system ranging from material source, process, assembling to testing. Most of our products have been certified to meet international safety standards, such as CE (LVD/EMC), CUL,FCC.

    2, Best Partner

    We have co-operative partner throughout the world including USA, Europe, South America, South Africa, Middle Eastern, India, Turkey, Pakistan, Iran and so on .We offer wide range quality products either from our own standard range or customer-made to your specifications. SORO is becoming the most growthful China UPS supplier all over the world.


    FAQ

    1. How to choose suitable inverter?


    If your load is resistive loads, such as: bulbs, you can choose a modified wave inverter. But if it is inductive loads and capacitive loads, we recommend using pure sine wave power inverter.


    For example: fans, precision instruments, air conditioner, fridge, coffee machine, computer, and so on.


    Modified wave can be started with some inductive loads, but effect for load using life,because capacitive loads and inductive loads need high quality power

    .......................................................................................................................................................................

    2. How do I choose the size of the inverter?


    Different types of load demand for power are different. You can view the load power values to determine the

    size of the power inverter.


    Notice:


    Resistive load: you can choose the same power as the load.


    Capacitive loads: according to the load, you can choose 2-5 times power.


    Inductive loads: according to the load, you can choose 4-7 times power.

    .......................................................................................................................................................................

    3. How connection between batteries and an power inverter?


    We usually believe that cables connecting battery terminal to inverter shorter is better. If you are just standard cable should be less than 0.5M, but should correspond to the polarity of the batteries and inverter-side outside. If you want to lengthen the distance between battery and inverter, please contact us and we will calculate the recommended cable size and length. Due to long distances using a cable connection, there will be a reduced voltage, which means that the inverter voltage would be far below the battery terminal voltage, this inverter will appear under voltage alarm conditions

    .......................................................................................................................................................................


    4. How to calculate the load of working hours requires configuration of the battery size?


    We will usually have a formula to calculate, but it is not hundred percent accurate, because there is also the battery's condition, the old batteries have some loss,so this is only a reference value:

    Work hours = battery capacity * battery voltage * 0.8/load power (H= AH*V*0.8/W)

    .......................................................................................................................................................................

    Quality High Frequency online UPS, Uninterrupted Power Supply 0.9 Output  10-20KVA for sale
    Send your message to this supplier
     
    *From:
    *To: Shenzhen SORO Electronics Co., Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Inquiry Cart 0