Sign In | Join Free | My chinalane.org
chinalane.org
Products
Search by Category
Home > Electronic Measuring Instruments >

Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line

Categories Fault Passage Indicator
Brand Name: Tianyihongda
Model Number: TYHD-AI1
Place of Origin: Beijing,China
MOQ: 1set(3pcs)
Price: Negotiation
Payment Terms: L/C,, T/T, Western Union
Supply Ability: 3000sets per week
Delivery Time: 3000 sets within 1 week
Packaging Details: 56*40*34cm,48 pcs /box ,standarad export box
Certification: type test report
applied inviroment: 6kv-110kv power distribution line
function: locate and detect short-circuit for overhead line
usage: locate and detect earth fault for overhead line
alarm: red flag and flashlight
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line

Fault Passage Indicator is installed on the overhead power lines, is to detect the grounded and short circuit fault for overhead line. It will alarm during the day and flash during night to show the fault. According to the alarm information , the operator can locate the fault area quickly and find out the point of fault, which supply the best solution for the difficulty in finding fault area. This device can improve work efficiency, reduce power outage time and power restoration quickly.The installation and uninstalling way is very simple and convenient.
The parameters can be modified by client's requirement. default paramters is as following:
  • voltage applicable: 6kV-110KV
  • long withstand current: 630A
  • Power distribution frequency: 50HZ/60HZ
  • protection grade: IP68
  • line diameter applicable: 16mm2≤d≤400mm2
  • load current measurement range: 25A-630A, variable within 10s, line load minimum lasting time is 10s.
  • Earthed alarm value: 45A, can be adjustable before delivery.
  • Short-circuit alarm value: 120-150-220-320-400-900A, sudden changed value is self-adaptable. (can be customized by client before delivery)
  • Fault recognition time: 40ms-10s
  • Fault shock lasting time (surge suppression time) : 10s
  • Alarm response time: 0.02S≤T≤3S
  • Static power consumption: ≤20μA
  • reset time: 6,12,24,48 hours,can be defined by client oneself before delivery..
  • Ambient temperature: -40℃≤T≤+75℃
  • Alarm times: ≥2000 times
  • Led flash total hours: 10000 hours
  • Led Flash period for permanent fault: one flash every three second(can be customized by client before delivery,red flag is available if required)
  • Led Flash period for transient fault:two flash every forty(twelve) second (can be customized by client before delivery, red flag is available if required)
  • Visible angel: 360 degrees, 40 Lumens.
  • Battery life: 10 years, not changeable.
  • weight: ≤500g
  • Humidity: ≤95%
  • Size:74mm*112.5mm

applied range

  • Installed middle section and branch entrance on long line: can indicate line fault section and fault branch.
  • installed at substation exit:Can judge the fault is happened inside or outside the station .
  • installed user distribution and transformation high voltage line entrance:can judge if the fault is caused by users.
  • installed in the connection point between cable and overhead line:can judge if the fault happened in cable section.

There is type test report for it, test items as following:

Type Test Items


1. appearance and structure 2.function 3. electrical device performance 4.low temperature performance 5.high temperature performance 6.alternating temperature humidity7.vibrationendurance 8.incline drop test 9. electrical device life 10. static electricity and elecro-discharge immunity test 11.radio frequency electromagnetic field radiated immunity test 12.surge impact immunity test 13. power frequency magnetic field immunity test. 14. Adjacent interference test 15.short-circuit withstand impact test 16. fire hazard test 17. power consumption test 18. protection grade test 19. gripping strength test of grip structure.
Quality Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line for sale
Send your message to this supplier
 
*From:
*To: Beijing Tianyihongda Science & Technology Development Co., LTD
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0